不同气候区数据中心用间接蒸发冷却空调的耗能分析  被引量:3

Energy consumption analysis of indirect evaporative cooling air conditioning for data centers in different climate zones

在线阅读下载全文

作  者:董新伟 耿永伟 郝亮 Dong Xinwei;Geng Yongwei;Hao Liang(China Academy of Building Research,Beijing)

机构地区:[1]中国建筑科学研究院有限公司,北京

出  处:《暖通空调》2023年第8期171-176,共6页Heating Ventilating & Air Conditioning

摘  要:为分析数据中心用间接蒸发冷却空调在我国各气候区的能耗情况,选取了5个气候区中11个城市分析单台间接蒸发冷却空调机组的年耗电量、年耗水量及年运行费用。研究结果表明:室外气候越干燥,间接蒸发冷却空调干模式运行时间越长;温和地区间接蒸发冷却空调的应用存在较大的节能潜力;高温高湿地区机组的年运行费用明显高于其他地区;与年运行电费相比,年运行水费占比很小。因此,进行数据中心空调设计时,应着重考虑空调系统的耗电量,以便减少能耗,降低电能利用效率(PUE)。In order to analyse the energy consumption of indirect evaporative cooling air conditioning for data centers in different climate zones in China,eleven cities in five climate zones are selected to analyse the annual power consumption,water consumption and operating costs of a single indirect evaporative cooling air conditioning unit.The results show that the drier the outdoor climate is,the longer the dry mode operation time of indirect evaporative cooling air conditioning is.The application of indirect evaporative cooling air conditioning to temperate zones has high energy saving potential.The annual operating cost of units in high temperature and humidity area is obviously higher than that in other areas.Compared with the annual operating electricity cost,the proportion of annual operating water cost is very small.So when designing air conditioning for data centers,the power consumption of air conditioning system should be considered to save energy and reduce the power utilization efficiency(PUE).

关 键 词:数据中心 气候区 间接蒸发冷却空调 年耗电量 年耗水量 年运行费用 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程] TU111.195

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象