摘 要:基于数值模拟方法建立了诊室通风模型,将上送上排、上送下排、地板送上排3种送风方式与2种换气次数(ACH=3/6 h^(-1))相结合,对比研究了6种通风方案对室内气流组织及污染物浓度分布的影响。采用吹风感指数、能量利用系数及污染物去除效率进行评价分析。结果表明:通过提高换气次数,室内CO_(2)浓度均能从超标状态降低至标准规定的1000×10^(-6)以内,且降幅均超过200×10^(-6);采用上送下排方案,有助于提高人员舒适性和送风能量利用系数,但污染物去除效率最低,无法有效去除室内污染物;采用地板送上排方案时,污染物去除效率最高,2种换气次数下分别为1.24和1.49,但在低风速下人员吹风感指数最高,影响人员舒适性,可通过提高换气次数有效缓解。A lack of ventilation and poor air quality in many buildings not only affect the learning efficiency of indoor occupants,but also cause sick building syndrome and even increase the risk of infectious diseases.As public spaces where health care workers look after patients with a complex mix of people,hospital outpatient clinics are highly crowded and are largely enclosed during consultations,so airflow and air quality requirements should be even more stringent.In order to avoid health problems caused by poor air quality,a reasonable and effective study on indoor airflow and air quality in hospital outpatient clinics is needed to ensure the quality of their indoor air environment.The existing studies on outpatient clinics mainly include the airflow in large spaces in outpatient buildings and the risk of indoor droplet exposure in outpatient clinics,without considering the evaluation of indoor personnel comfort and contaminant removal efficiency.There is a lack of multi-perspective evaluation research on indoor airflow organization,indoor air quality and personnel comfort in outpatient clinics.Therefore,to improve the comfort and safety of people in hospital outpatient clinics,this paper conducts indoor air quality tests for hospital outpatient clinics,and establishes a ventilation model of outpatient clinics based on the numerical simulation method.It combines the three air supply modes(upper air supply and upper exhaust,upper air supply and lower exhaust,and under floor air supply and upper exhaust)with two exchange times per hour(ACH=3/6 h-1).The effects of six ventilation schemes on the indoor air distribution and contaminant concentration are compared and studied.Draught rate,energy utilization coefficient and contaminant removal efficiency are used for evaluation and analysis.The results show that:(1)An experimental study of outpatient clinics in a hospital in Taiyuan reveals that the indoor air quality in consultation rooms is poor.All eight consultation rooms measured have a concentration that exceeds the st
分 类 号:TU834[建筑科学—供热、供燃气、通风及空调工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.16.188.113