检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:车腾腾 王家良 CHE Tengteng;WANG Jialiang(Sichuan Provincial Architectural Design and Research Institute Co.,Ltd.,Chengdu 610017,China)
机构地区:[1]四川省建筑设计研究院有限公司,成都610017
出 处:《给水排水》2023年第7期108-111,共4页Water & Wastewater Engineering
摘 要:根据《消防给水及消火栓系统技术规范》3.5.3条要求,当建筑物设置自动喷水灭火系统时,多层建筑室内消火栓设计流量可折减50%,高层建筑内消火栓设计流量可减少5L/s。相关规范宜要求适时扩大民用建筑上自动喷水灭火系统的设置范围;按此条文要求在实际工程项目上酌情采用,可提升建筑实际消防安全性,同时未必增加工程项目的建安成本。According to 3.5.3 requirements of the national standard Technical code for fire protection zwater supply and hydrant systems,when the automatic sprinkler system is installed in the building,the designed flow rate of the multi-story building indoor fire hydrant can be reduced by 50%,and the designed flow rate of the high-rise building fire hydrant can be reduced by 5 L/s.This paper considers that the relevant regulations should be required to expand the setting scope of automatic sprinkler system in civil buildings in a timely manner,according to this provision,should be adopted as appropriate in actual engineering projects,can enhance the actual fire safety of the building,and may not increase the construction safety cost of projects.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.15