摘  要:介绍了一起区外故障引起主变压器差动保护越级跳闸事故的相关情况,通过对现场相关保护设备、二次回路进行特性试验、绝缘试验及测量,并对保护装置动作报告和事故录波进行分析,确定是变压器高压侧中性线接触不良,故障时无自产零序电流,高压侧电流发生畸变,而导致的差动保护跳闸。得出的结论为保护正确动作。In this paper,the related situation of a major transformer differential protection tripping accident caused by an outof-area fault is introduced.Based on the characteristics test,insulation test and measurement of the field related protection equipment and secondary circuit,and an analysis of the action report of protective device and accident recording,it is determined that the neutral line on the high voltage side of the transformer is in poor contact.As there is no self-generated zero sequence current at fault and the high voltage side current is distorted,differential protection trip occurs.The conclusion is that this is the correct protection action.