GIS设备中CT接线座开裂失效分析  

Analysis on CT Wiring Base Cracking in GIS Equipment

在线阅读下载全文

作  者:周延科 张素慧 李军 张兆钰 赵朝友 ZHOU Yanke;ZHANG Suhui;LI Jun;ZHANG Zhaoyu;ZHAO Chaoyou(State Grid Gansu Electric Power Science Research Institute,Lanzhou 730070;Gansu Electric Power Research Institute Technology Center Co.,Ltd.,Lanzhou 730070)

机构地区:[1]国网甘肃省电力公司电力科学研究院,甘肃兰州730070 [2]甘肃电力科学研究院技术中心有限公司,甘肃兰州730070

出  处:《电力安全技术》2023年第7期28-30,共3页Electric Safety Technology

摘  要:针对某换流站内GIS中发生的漏气故障进行宏观检查、渗透检测和受力分析,结果表明,本次漏气故障是由CT接线座开裂导致,采用不当的紧固工具或用力过大,造成不连续部位承受过大的弯曲应力,造成接线座开裂,提出的预防措施可供参考。In allusion to the gas leakage fault in the GIS of a converter station,analyses were conducted by macroscopic inspection,penetration test and force analysis.The results showed that the air leakage fault was caused by the cracking of CT wiring base.The use of improper fastening tools or excessive force brought about excessive bending stress on the discontinuous parts,resulting in the cracking of the wiring base,which is available for reference in putting forward preventive measures.

关 键 词:CT接线座 裂纹 受力分析 仿真计算 

分 类 号:TM561.3[电气工程—电器]

 