检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:甘永忠
机构地区:[1]中国铁路兰州局集团有限公司供电部
出 处:《电气化铁道》2023年第S01期29-32,共4页Electric Railway
摘 要:部分运行故障表明,接触网隔离开关的电源和控制电缆成为强电侵入变电所二次系统的入口,进而烧损变电所内电源和保护等设备,持续的大电流造成所内设备的严重破坏。本文重点对强电侵入变电所二次系统的机理、破坏能量及径路进行深入分析,并对《牵引变电所二次系统防强电侵入优化技术方案指导意见》中多项具体措施在实践应用中出现的问题和适用性作进一步探讨。A part of operational failures show that:the power source and control cables of OCS disconnector become the entrance of the strong current intruding into the secondary system of substation.Then the power source and protection equipment are burnt down by the intruded strong current,and the continuous high current will lead to severe damage of equipment inside the substation.The paper analyzes with emphasis the mechanism,destruction energy and path of strong current intruding into the secondary system of substation,further discusses the problems occurred during the implementation and application of several measures specified in Guidance on Scheme for Technical Optimization of Preventing Strong Current Intruding into the Secondary System of Traction Substation and their adaptability.
分 类 号:U224.3[交通运输工程—道路与铁道工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.171