作 者:郭超 刘烜 曹泽昊 刘碧武 田源硕 GUO Chao;LIU Xuan;CAO Ze-hao;LIU Bi-wu;TIAN Yuan-shuo(Yalong River Hydropower Development Company.Ltd.,Chengdu 610051,China)
机构地区:[1]雅砻江流域水电开发有限公司,四川成都610051
出 处:《云南水力发电》2023年第9期278-281,共4页Yunnan Water Power
摘 要:水喷雾灭火系统是水电站主变压器发生火灾时的主要灭火手段,但近年来因雨淋阀误动而导致水喷雾装置误喷淋的情况时有发生。结合某水电站一起主变水喷雾灭火系统误喷淋事件,对误喷淋原因进行研究和分析,指出水喷雾灭火系统在实际应用中存在的隐患,通过改造排水阀、定期检查逆止阀、取下紧急手动阀操作手柄等措施,降低水喷雾灭火系统误动的风险。Water spray extinguishing system is the main means of extinguishing fire in the main transformer of hydropower station.However,in recent years,the water spray device mistakenly sprays due to the misoperation of the deluge valve.Combined with an accident of mistakenly spraying the main transformer water spray fire extinguishing system in a hydropower station,this paper studies and analyzes the causes of mistakenly spraying.It points out the hidden dangers of water spray fire extinguishing system in practical application.The risk of misoperation of the water spray fire extinguishing system is reduced through measures such as reforming the drain valve,regularly checking the check valve,and removing the operating handle of the emergency manual valve.
分 类 号:TV737[水利工程—水利水电工程]