作 者:涂春鸣[1] 杨万里 肖凡[1] 郭祺[1] 何西 TU Chunming;YANG Wanli;XIAO Fan;GUO Qi;HE Xi(National Electric Power Conversion and Control Engineering Technology Research Center,Hunan University,Changsha 410082,China;College of Electrical and Information Engineering,Hunan Institute of Technology,Hengyang 421002,China)
机构地区:[1]湖南大学国家电能变换与控制工程研究中心,湖南长沙410082 [2]湖南工学院电气与信息工程学院,湖南衡阳421002
出 处:《电力自动化设备》2023年第9期55-62,94,共9页Electric Power Automation Equipment
基 金:国家自然科学基金资助项目(52077072)。
摘 要:当电网发生严重故障时,虚拟同步发电机(VSG)易发生功角失稳并导致故障电流越限,现有方法大多忽略功角失稳与故障过流之间的内在关联性而将二者单独处理,导致二者难以同时解决.为此,分析了VSG的暂态功角特性和故障电流特性,阐释了产生上述问题的原因及相互关系;基于相图理论分析了多影响因素下VSG的暂态功角稳定性,提出了一种考虑故障限流的VSG暂态功角稳定控制方法,该方法在自适应调节有功功率指令以保持功角稳定的基础上联合调节无功调压系数,并引入准静态近似虚拟阻抗,同时实现了故障期间VSG的暂态功角稳定和全故障限流.仿真和实验结果验证了理论分析的正确性及所提控制方法的有效性.When a serious fault occurs in the power grid,the virtual synchronous generator(VSG)is prone to power angle instability and fault current exceeding the limit.Most of the existing methods ignore the internal correlation between power angle instability and fault overcurrent and deal with them separately,which makes it difficult to solve the two problems simultaneously.Therefore,the transient power angle cha-racteristic and fault current characteristic of VSG are analyzed,and the causes and relations of the above problems are explained.Based on the phase diagram theory,the transient power angle stability of VSG under multiple influencing factors is analyzed,and a transient power angle stability control method of VSG considering fault current limitation is proposed.On the basis of adaptively adjusting the active power com⁃mand to keep the power angle stable,the proposed method regulates the reactive power regulation coeffi⁃cient jointly.In addition,a quasi-static approximate virtual impedance is introduced to realize both transient power angle stability and total fault current limitation of VSG during fault.Simulative and experimental results verify the correctness of the theoretical analysis and the effectiveness of the proposed control method.
关 键 词:虚拟同步发电机 对称短路故障 暂态功角稳定控制 故障限流 电压跌落 联合调节
分 类 号:TM712[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.147