一起全厂停电事故原因分析及处理过程  被引量:1

Analysis and Treatment of a Power Failure of the Whole Plant

在线阅读下载全文

作  者:赵磊 ZHAO Lei(Guodian Tongling Power Generation Co.,Ltd.,Tongling 244100,China)

机构地区:[1]国能铜陵发电有限公司,安徽铜陵244100

出  处:《安徽电气工程职业技术学院学报》2023年第3期8-11,共4页Journal of Anhui Electrical Engineering Professional Technique College

摘  要:大型汽轮发电机在出现全厂送出线路故障、功率突降的工况下跳闸,可以避免对热力系统的危害,但也会导致全厂停电事故的发生。文章描述了某电厂因冰雪灾害导致双回路出线同时故障停电,对电厂两台机组零功率切机保护动作造成全厂停电事故原因进行分析,并对全厂停电后机组处理原则进行探讨。The trip of large turbo-generator under the condition of transmission line fault or sudden power drop can avoid the harm to the thermal system,but it will also lead to the occurrence of power failure of the whole plant.This paper describes the double circuit outlet fault due to a snow and ice disaster,analyzes the power failure of the whole plant caused by the zero power cut protection action of two units of a power plant,and discusses the principle of unit treatment after power failure of the whole plant.

关 键 词:线路故障 零功率切机保护 全厂停电 故障处理 

分 类 号:TM621.28[电气工程—电力系统及自动化]

 