作  者:吕晏 徐荣吉[1] 李晓娜 吴青平[2] 王瑞祥[1] LU Yan;XU Rongji;LI Xiaona;WU Qingping;WANG Ruixiang(Beijing Engineering Research Center of Sustainable Energy and Buildings,Beijing University of Civil Engineering and Architecture,Beijing 100044,China;School of Energy and Power Engineering,Xi'an Jiaotong University,Xi'an 710049,China)

机构地区:[1]北京建筑大学北京市建筑能源高效综合利用工程技术研究中心,北京100044 [2]西安交通大学能源与动力工程学院,陕西西安710049

出  处:《热科学与技术》2023年第4期372-380,共9页Journal of Thermal Science and Technology

基  金:国家自然科学基金资助项目(51506004);国家重点研发计划资助项目(2020YFF0303904);北京市自然科学基金资助项目(3162009);北京建筑大学研究生创新资助项目(PG2023064);北京建筑大学基本科研业务费资助项目(X20065,X18263)。

摘  要:将多片平板微热管阵列进行堆叠可以提高传热量。实验研究了不同叠加片数下平板微热管阵列在不同加热功率下的热阻、传热极限、温度分布及变化规律、不同层热管传热等运行特性。实验表明:随热管片数增加,热管整体的传热量增加,最大传热量由单片的60.0 W提升至5片的180.0 W;传热热阻降低,最小传热热阻由单片的1.09℃/W下降为5片的0.24℃/W。而且,随着片数增加,热管间的传热热阻开始影响多片平板微热管阵列的整体运行:外侧热管的传热量高于内侧热管,热阻低于内侧热管,且当片数为4片及以上时,热管整体性能提升会越来越不明显。在相同的加热功率下,多片平板微热管阵列的外侧蒸发段、外侧冷凝段和内侧蒸发段温度均随片数增加而降低,但内侧冷凝段温度先升高后降低。最理想的热管叠加片数为3~4片。Stacking multiple plate micro-heat pipe arrays can improve heat transfer.The thermal resistance,heat transfer limit,temperature distribution and variation,heat transfer of different layers of heat pipe array under different heating powers were studied experimentally.The results show that with the increase of the number of heat pipes,the overall heat transfer increases,and the maximum heat transfer increases from 60.0 W of single heat pipe to 180.0 W of five heat pipes.The minimum heat transfer resistance decreased from 1.09℃/W for single chip to 0.24℃/W for 5 chips.Moreover,with the increase of the number of plates,the heat transfer resistance between heat pipes begins to affect the overall operation of the multi-plate micro heat pipe array:the heat transfer of the outer heat pipe is higher than that of the inner heat pipe,while the heat resistance is lower than that of the inner heat pipe.When the number of plates is 4 or more,the overall performance improvement of the heat pipe will be less and less obvious.Under the same heating power,the temperatures of the outer evaporation section,the outer condensation section and the inner evaporation section of the multi-plate micro heat pipe array decrease with the increase of the number of plates,but the temperature of the inner condensation section increases first and then decreases.The ideal number of heat pipe stacking is 3-4 pieces.

关 键 词:热管 运行特性 传热极限 热阻 

分 类 号:TK172.4[动力工程及工程热物理—热能工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象