检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:李小鹏 张华杰 吴嘉煜 周文越 LI Xiaopeng;ZHANG Huajie;WU Jiayu;ZHOU Wenyue(State Grid Sichuan Electric Power Research Institute,Chengdu 610041,Sichuan,China;School of Electrical Engineering,Southwest Jiaotong University,Chengdu 610031,Sichuan,China)
机构地区:[1]国网四川省电力公司电力科学研究院,四川成都610041 [2]西南交通大学电气工程学院,四川成都610031
出 处:《四川电力技术》2023年第5期1-6,94,共7页Sichuan Electric Power Technology
基 金:四川省重点研发计划项目(2021YFG0101);国网四川省电力公司研究开发项目(52199720002H)。
摘 要:针对城市电网直流偏磁主变压器中性点安装隔直装置后,导致周围其他主变压器中性点直流增加出现直流偏磁这一现象,提出研究隔直装置安装位置对城市电网主变压器直流偏磁电流分布的影响。考虑地铁回流系统结构、换乘站综合接地系统连接特征以及地铁和城市电网空间、电气连接关系,基于CDEGS仿真软件建立西南某城市电网及地铁网络耦合模型。在此基础上,仿真分析了不同类型变电站安装隔直装置后,电网变电站主变压器直流偏磁电流幅值变化特征。分析结果表明,为地铁主变电所供电的220 kV变电站安装隔直装置后,与其直连的变电站主变压器直流偏磁电流总量减少超过15%,能够显著抑制直流偏磁电流,为城市电网变电站隔直装置安装位置确定提供理论依据。A study on the influence of installation position of DC blocking devices on DC magnetic bias current distribution of main transformer in urban power grid is proposed after the installation of DC blocking devices at the neutral point of main transformer in urban power grid,which leads to the increase of DC at the neutral point of the surrounding main transformers and the phenomenon of DC bias magnetization.By considering the structure of subway return system,the grounding system of transfer stations and the spatial and electrical connection relationship between subway and urban power grid,a coupling model of urban power grid and subway network for a city in southwest China is established based on CDEGS simulation software.On this basis,the simulation analyzes the characteristics of amplitude change of DC magnetic bias current of main transformer in grid substation after the installation of DC blocking devices in different types of substations.The analysis results show that after installing DC blocking devices in 220 kV substation supplying the metro main substation,the total DC magnetic bias current of substation which directly connected to it is reduced more than 15%,which can significantly suppress the DC magnetic bias current and provides a theoretical basis for the determination of installation position of DC blocking devices in substations of urban power grid.
关 键 词:隔直装置安装位置 地铁杂散电流 城市电网 主变压器直流偏磁电流
分 类 号:TM74[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.30