摘  要:热电偶的快速响应特性使其在工业过程测量中有非常广泛的应用,然而由于毫伏信号的传输存在易受干扰影响的性质,在实际使用中经常遇到干扰的问题。文章就加热炉热电偶使用中的故障案例,讨论了热电偶的测量原理,测量回路以及屏蔽层的干扰问题,针对该案例中的故障找到了产生的原因,即电缆屏蔽层的腐蚀以及虚接。之后提出了解决方法,优化屏蔽层接线形式,并对屏蔽层实施保护性措施。该处理方法在后续的生产实践中得到了验证,大大降低了加热炉热电偶的故障率。the rapid response characteristic of thermocouple makes it widely used in industrial process measurement.However,the transmission of millivolt signal is susceptible to interference,in the actual use of frequent interference problems.In this paper,the measuring principle of thermocouple,the interference of measuring circuit and shielding layer are discussed,the causes of the faults in this case are found:corrosion of the cable shielding layer and virtual connection.The solution is to optimize the wiring form of the shielding layer and carry out protective measures for the shielding layer.The treatment method has been verified in the following production practice,and the failure rate of heating furnace thermocouple has been greatly reduced.