作 者:叶伟豪 郭强 赵兵 兰天楷 YE Weihao;GUO Qiang;ZHAO Bing;LAN Tiankai(China Electric Power Research Institute,Haidian District,Beijing 100192,China)
机构地区:[1]中国电力科学研究院有限公司,北京市海淀区100192
出 处:《电网技术》2023年第11期4377-4385,共9页Power System Technology
基 金:国家重点研发计划项目(响应驱动的大电网稳定性智能增强分析与控制技术)(2021YFB2400800)。
摘 要:在高比例可再生能源并网的背景下,新型电力系统的建设和安全高效运行与大规模并网逆变器的动态特性密切相关。目前针对电压源型逆变器并网系统的研究大多将多机系统视为单机系统展开分析,实际上,电压源型逆变器多机间存在着交互作用且不容忽视,因此该文对多机系统展开了研究。该文从外环控制的角度出发,建立了电压源型逆变器单、双机系统小信号模型,采用特征值分析、参与因子理论和电磁暂态仿真分析相结合的方式,对比分析了定功率因数控制、混合控制策略、交流侧恒定电压控制3种不同外环控制策略对双机系统的影响,揭示了定功率因数控制的失稳机理。研究的结果和结论表明:电压源型逆变器多机系统采用混合控制策略并网更有利于功率向外输送;交流侧恒定电压控制方式的响应速度主要受到有功控制环节积分增益的影响;定功率因数控制受限于无功调节能力不足和控制环节的延时,在弱电网下稳定性较差。Under the background of high proportion of renewable energy,the construction and safe operation of novel power system are closely related to the dynamic characteristics of large-scale grid-connected inverters.At present,most of the researches on voltage source converter(VSC)grid connected system take the multi-VSCs system as a single machine system.In fact,there is interaction between multi-VSCs and it can not be ignored.Therefore,this paper studies the multi-VSCs system.From the point of view of VSC’s outer loop,this paper establishes the small signal model of VSC single machine and dual machine systems.By using the combination of eigenvalue analysis,participation factor theory and electromagnetic transient simulation analysis,the influence of three different outer loop control strategies,namely constant power factor control,hybrid control strategy and alternating current(AC)side constant voltage control,on dual machine systems is analyzed and compared,and the instability mechanism of constant power factor control is revealed.The results and conclusions show that the hybrid control strategy of multi-VSCs system is more conducive to power outward transmission.The response speed of AC-side constant voltage control mode is mainly affected by the integral gain of active power control loop;the constant power factor control is limited by the insufficient reactive power regulation ability and the delay of the control loop,and its stability is poor under the weak grid.
关 键 词:电压源型逆变器 小信号模型 外环控制 参与因子 多机交互 控制协调性
分 类 号:TM721[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.189.186.244