油浸式变压器导油板对油流特性与温度分布的影响  被引量:1

Oil-guiding Plate Effect on the Oil Flow Characteristics and Temperature Distribution of Oil-immersed Transformer

在线阅读下载全文

作  者:刘锐 赵振喜 郑存龙 高峰 刘欣 吴龙飞 LIU Rui;ZHAO Zhen-xi;ZHENG Cun-long;GAO Feng;LIU Xin;WU Long-fei(NARI Technology Nanjing Control Systems Co.,Ltd.;State Grid Jilin Electric Power Co.,Ltd.;Construction Branch of State Grid Jilin Electric Power Co.,Ltd.)

机构地区:[1]国电南瑞南京控制系统有限公司 [2]国网吉林省电力有限公司 [3]国网吉林省电力有限公司建设分公司

出  处:《化工自动化及仪表》2023年第6期865-874,共10页Control and Instruments in Chemical Industry

基  金:国网吉林省电力有限公司智慧变电站建设关键技术科技基金(批准号:522371210003)资助的课题。

摘  要:变压器的绕组和绝缘油之间散热不均导致绕组局部热点温度过高,影响绝缘材料的绝缘特性。为研究油道和导油板对变压器油的流速、流向以及热点温度的影响,首先对变压器流体域、固体域以及流-固交界面上的传热模型进行分析,确定了流-固界面的传热数学模型。基于此,构建并求解了油浸式变压器数值仿真模型,利用变压器温升试验结果验证了数值模型的准确性。最后,在数值模型中研究了两种横向导油板对变压器油的流场和温度分布的影响。研究表明:基于流-固耦合特性构建的数值模型温度偏差小于1℃时,横向挡油板使水平油流平均油速和峰值流速分别提高1.4倍和2.3倍,提高了流-固耦合区域的换热效率,绕组平均温度和热点温度下降3℃以上,为变压器绕组散热分析与结构设计提供了新方法。The nonuniformity of heat dissipation between transformer winding and insulation oil can cause higher local hot-spot temperature of the winding,which affects insulation characteristics of the insulation materials.For purpose of investigating both oil channels and oil guide plates’effect on the transformer oil’s velocity,flow direction and hot spot temperature,analyzing heat transfer models of the transformer fluid domain,solid domain and the fluid-solid intersection interface was implemented and the mathematical model of the heat transfer at the fluid-solid interface was determined.Based on this,the numerical simulation model of the oil-immersed transformer was constructed and solved,and having transformer temperature rise test results based to verify accuracy of the numerical model.Finally,in a numerical model,the effects of two transverse oil-guiding plates on the transformer oil’s flow field and temperature distribution were studied.The results show that,the numerical model’s deviation based on the fluid-structure interaction characteristics is less than 1℃,and the transverse oil deflector increases average oil velocity and peak flow velocity by 1.4 times and 2.3 times,respectively,and the heat transfer efficiency in fluid-structure interaction area is improved.The average temperature and hot-spot temperature of the winding are decreased by more than 3℃,which provides a new method for analysis and design of transformer winding heat dissipation.

关 键 词:油浸式变压器 油流速度 油流方向 温度分布 导油板 

分 类 号:TK311[动力工程及工程热物理—热能工程]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象