天然气管道压缩机组DCP/UPS电源的安全环保节能改造  被引量:1

SAFETY,ENVIRONMENTAL PROTECTION AND ENERGY CONSERVATION REVAMP OF DCP/UPS POWER SUPPLY FOR COMPRESSOR UNIT IN NATURAL GAS PIPELINE

在线阅读下载全文

作  者:刘风明 吕开钧 范文涛 郑会 李江宁 隋学礼 王岩 杨新平 Liu Fengming;Lyu Kaijun;Fan Wentao;Zheng Hui;Li Jiangning;Sui Xueli;Wang Yan;Yang Xinping(PipeChina West Pipeline Co.,Ltd.,Urumqi,Xinjiang,830000;West-East Gas Transmission Branch of National Pipe Network Group United Pipeline Co.,Ltd.,Shanghai,200122;South-East Asia Gas Pipeline Company Limited,Beijing,100000;PipeChina Beijing Pipeline Co.,Ltd.,Beijing,100000;Qingdao Gomatech Development Co.,Ltd.,Qingdao,Shandong,266101)

机构地区:[1]国家管网集团西部管道有限责任公司,新疆乌鲁木齐830000 [2]国家管网集团西气东输分公司,上海200122 [3]东南亚天然气管道有限公司,北京100000 [4]国家管网集团北京管道有限公司,北京100000 [5]青岛创统科技发展有限公司,山东青岛266101

出  处:《石油化工安全环保技术》2023年第4期30-34,I0002,共6页Petrochemical Safety and Environmental Protection Technology

摘  要:我国天然气管道初期工程中大量采用国外先进压缩机技术,由于其采用国外标准和根据国外供电条件设计,在我国的实际应用中产生很多问题,供电问题是其中的一种。文章基于目前天然气压气站供电状况存在的问题,提出了采用国产电源替代的节能改造方案。改造前的DCP/UPS电源采用相控模式,效率只有70%左右,改造后效率可提高至92%。DCP/UPS电源改造已在西气东输、西部管道及陕京线成功改造了50多套。实践证明:用国产DCP/UPS电源替代,不仅设计合理、运行可靠,维护方便,而且备件充足、成本低。A large number of foreign advanced compressor technologies were adopted in the initial projects of China’s natural gas pipeline.And because they were designed by adopting foreign standards and according to foreign power supply conditions,many problems arose from their practical application in China,of which the problem of power supply is one of them.Based on the problems existing in the current power supply of natural gas compressor stations,this paper proposed an energy conservation revamp program using substitution of domestic power supply.Before the revamp,the DCP/UPS power supply was in phase-controlled mode with an efficiency of only about 70%,and the efficiency can be increased to 92% after the revamp.DCP/UPS power supply revamp has been successfully carried out in more than 50 sets in West-East Gas Pipeline,Western Pipeline and Shaanxi-Beijing Pipeline.Practice has proved that with the domestic DCP/UPS power supply replacement,the design is reasonable;the operation is reliable and the maintenance is convenient.In addition,the spare parts are sufficient and the cost is low.

关 键 词:DCP/UPS 逆变模块 直流模块 监控单元 节能 

分 类 号:TE973[石油与天然气工程—石油机械设备]

 