CFD仿真在数据中心孔板送风气流组织中的应用研究  

Application Research of CFD Simulation in Orifice Air Distribution of Data Center

在线阅读下载全文

作  者:李虹晔 郑伟 霍世诰 Li Hongye;Zheng Wei;Huo Shigao(Taiji Computer Co.,Ltd.,Beijing 100102.China;Beijing Haiwu Technology Co.,Ltd,Beijing 100089,China)

机构地区:[1]太极计算机股份有限公司,北京100102 [2]北京海悟技术有限公司,北京100089

出  处:《绿色建造与智能建筑》2023年第11期96-99,共4页GREEN CONSTRUCTION AND INTELLIGENT BUILDING

摘  要:以某数据中心为例,基于多孔介质模型理论和CFD仿真对静压箱孔板送风的开孔率进行了研究,通过理论计算得出合适的开孔率范围来指导模拟,通过模拟得出的压力场、温度场和速度场验证了理论计算结果,发现在开孔率为25~50%时,机房内压力场、温度场和速度场均符合机柜正常运行要求,气流组织合理,机柜无热点现象,并且确定了机房空调的最不利故障点。Taking a data center as an example,based on multi-void medium model theory and CFD simulation,the opening ratio of orifice plate air supply of static pressure box was studied.The appropriate opening ratio range was obtained through theoretical calculation to guide the simulation.The theoretical calculation results were verified by the pressure field,temperature field and velocity field obtained through simulation.It was found that when the opening ratio was 25~50%,the pressure field,temperature field and velocity field in the machine room met the normal operation requirements of the cabinet,and the air flow organization was reasonable,There is no hot spot in the cabinet,and the most unfavorable fault point of the air conditionerin the machineroom is determined.

关 键 词:CFD 数据中心 气流组织 开孔率 

分 类 号:TP308[自动化与计算机技术—计算机系统结构]

 