消防给水系统加压泵自动启动与手动启停控制在工程设计中的应用  被引量:2

Application of Automatic Start and Manual Start Stop Control of Booster Pump in Fire Water Supply System in Engineering Design

在线阅读下载全文

作  者:高居铃 Gao Juing(Times Architecture Design Institute(Fujian)Co.Ltd.,Fuzhou,Fujian 350013)

机构地区:[1]时代建筑设计院(福建)有限公司,福建福州350013

出  处:《江西建材》2023年第9期212-213,216,共3页Jiangxi Building Materials

摘  要:消防水泵通过出水干管上的压力开关、高位消防水箱出水管上的流量等信号,能自动启动。文中通过压力开关设置位置及对自动启泵信号动作压力值的计算,分析流量开关设置位置,以及自动启泵信号动作流量值的设定,直接启动消防泵,无需通过联动控制器。The fire pump should be automatically started by the pressure switch on the main outlet pipe of the fire pump and the flow signal on the outlet pipe of the high-level fire water tank.The article analyzes the setting position of the pressure switch and the calculation of the automatic pump start signal action pressure value,and analyzes the setting position of the flow switch and the seting of the automatic pump start signal action flow value.Directly starting the fire pump does not rely on the linkage controller.

关 键 词:自动启动 手动启停 压力开关 启泵压力值 

分 类 号:TU991[建筑科学—市政工程]

 