作 者:吴宇奇 肖澍昱 黎钊 李正天[1] 林湘宁[1] Wu Yuqi;Xiao Shuyu;Li Zhao;Li Zhengtian;Lin Xiangning(State Key Laboratory of Advanced Electromagnetic Engineering and Technology Huazhong University of Science and Technology,Wuhan 430074 China)
机构地区:[1]强电磁工程与新技术国家重点实验室(华中科技大学),武汉430074
出 处:《电工技术学报》2023年第24期6695-6708,共14页Transactions of China Electrotechnical Society
基 金:国家重点研发计划资助项目(2021YFB2401000)。
摘 要:针对现有的交流电网相继速动保护判据的可靠性能受限于运行工况与系统参数,以及其无法耐受较高过渡电阻的难题,该文首先研究了本级线路盲区故障与下级线路故障时由对端断路器开断产生的二次振荡波过程的差异性,并基于行波模量网络分析了特定故障工况下的特殊波过程;然后,提出了基于数学形态学梯度算法的振荡波头极性辨识判据以及特殊故障工况下的辅助判据,以形成全新的相继速动保护判据;最后,基于PSCAD仿真平台验证了所提保护判据的有效性、灵敏性与可靠性,其适用于三相/单相跳闸方式、适应于所有故障类型、不受系统运行工况与系统参数影响,同时耐受过渡电阻能力高达300Ω。Currently,high-voltage/ultra-high-voltage transmission lines mainly adopt unit protections as their main protection.However,considering communication failure,transmission time delay,and expensive construction cost for unit protections,non-unit protections,such as impedance relays,as complementary protection functions with the unit protections,play an indispensable role in the safe operation of the power grid.Due to protection selectivity and reliability,it is difficult for non-unit protections to cover the full length of the protected line.That is,there is a protection non-detection zone,usually the high-resistance zone within the protection scope,and all zones outside the protection scope of the protected line.In order to accelerate the fault clearing in the non-detection zone,non-unit protections must realize reliable identification of non-detection zone faults,namely,the fast sequential action principle.Therefore,many scholars have presented many achievements in early research.However,the performance of the existing fast sequential action principle is limited by operating conditions and system parameters,and they cannot withstand high fault resistance.Therefore,constructing a novel fast sequential action principle to overcome the above problems is urgent.This paper presents a novel fast sequential action principle based on the secondary oscillating traveling waves generated by remote circuit breaker operation.Firstly,the differences in the secondary oscillating traveling waves process under the internal non-detection zone and external faults are studied using the Bewley lattice diagram.The secondary oscillating traveling waves under different fault locations exhibit significant differences in oscillatory period and wave front polarity.Secondly,the local relay can always detect the secondary oscillating traveling waves generated by faults on the adjacent line.However,for the secondary oscillating traveling waves generated by internal fault,whether it can be effectively detected needs to analyze the reflection a
关 键 词:相继速动 二次振荡波 数学形态学梯度 盲区故障 行波模量网络
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.226.169.66