间接蒸发制冷高效集成冷站应用及分析  被引量:1

Application and Analysis of Indirect Evaporative Refrigeration and Efficient Integrated Refrigeration Station

在线阅读下载全文

作  者:张帅 程序[1] 王占军[1] 王凯 丁昊 Zhang Shuai;Cheng Xu;Wang Zhanjun;Wang Kai;Ding Hao(China Information Technology Designing&Consulting Institute Co.,Ltd.,Beijing 100048,China)

机构地区:[1]中讯邮电咨询设计院有限公司,北京100048

出  处:《邮电设计技术》2023年第12期46-49,共4页Designing Techniques of Posts and Telecommunications

摘  要:通过对某机房应用的间接蒸发制冷高效集成冷站系统进行详细介绍,阐述了该冷源系统在数据中心、通信机房应用的安全性及节能性,并通过对应用数据的实测分析,证明了间接蒸发制冷高效集成冷站可提供比传统冷却塔低5~8℃的冷水,延长自然冷却的应用时间,相较于机房原风冷精密空调,实现50%以上节能率。Through the detailed introduction of the indirect evaporative refrigeration high-efficiency integrated refrigeration station sys-tem applied in a computer room,the safety and energy-saving performance of the cold source system in the data center and communication room are expounded,and through the measurement and analysis of the application data,it is proved that the indirect evaporative refrigeration high-efficiency integrate refrigeration station can provide cold water 5~8°C lower than the traditional cooling tower,prolong the application time of natural cooling,and achieve more than 50%energy saving rate com-pared with the original air-cooled precision air conditioning in the computer room.

关 键 词:数据中心 间接蒸发 集成冷站 节能 

分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]

 