作 者:王笑非 王静舞 刘志宏 叶瑾 郑晓东 WANG Xiaofei;WANG Jingwu;LIU Zhihong;YE Jin;ZHENG Xiaodong(Hefei Institute for Public Safety Research Tsinghua University,Hefei,Anhui Province 230601,China;Yunnan Branch of China National Tobacco Corporation,Kunming,Yunnan Province 650011,China)
机构地区:[1]清华大学合肥公共安全研究院,安徽合肥230601 [2]中国烟草总公司云南省公司,云南昆明650011
出 处:《中国人民警察大学学报》2024年第2期51-57,共7页Journal of China People's Police University
基 金:中国烟草总公司云南省公司科技计划项目“云南烟草商业智慧消防体系建设与关键技术研究”(2022530000241025)。
摘 要:通过缩尺寸模型试验研究烟草高架仓库顶棚、端墙、侧墙和货架及货物等形成的特殊遮挡结构微元对火灾早期烟气蔓延规律的影响,结合不同火源位置条件下火灾探测器预警情况,提出6种火灾自动报警系统耦合方案并分析报警有效性。结果表明:火源位于底层时烟气在竖向蔓延过程中紧贴货架及货物侧面,撞击端墙后形成反浮力壁面射流;火源位于顶层时,特殊遮挡结构微元的空腔成为储烟区域,火灾早期未出现反浮力壁面射流。线型感温与吸气式感烟火灾探测器组成的火灾自动报警组合,报警响应时间较短,环境敏感性较低,报警有效性较高。线型感温和图像型火灾探测器组成的报警组合存在探测盲区,环境敏感性高,报警有效性较低。The effectiveness of the automatic fire alarm system of high-bay tobacco warehouse was studied through the 1/4 scaled model experiment in which the influence of the special shielding structure formed by the ceiling,end wall,side wall,shelves and goods of the high-bay tobacco warehouse on the early-stage smoke spread law of the fire was analyzed,6 automatic fire alarm system coupling schemes were proposed based on the fire detector early warn⁃ing situation under different fire source locations.The results show that when the fire source is located in the bottom layer,the smoke sticks to the shelves and the side of the goods in the vertical spreading process,and forms the antibuoyancy wall jet after hitting the end wall;when the fire source is located on the top floor,the cavity of the special shielding structure becomes the smoke storage area,and there is no anti-buoyancy wall jet in the early stage of the fire.The automatic fire alarm system composed of the inspiratory smoke detector and the linear temperature fire detector has shorter alarm response time,lower environmental sensitivity and higher response effectiveness.The automatic fire alarm system composed of linear temperature detector and image fire detector has detection blind spots,high environmental sensitivity and low response effectiveness.
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7