主变复压过流保护的电压整定及灵敏度校验  被引量:1

Voltage Setting and Sensitivity Checking of MT Complex Voltage Overcurrent Protection

在线阅读下载全文

作  者:邢瑞江 张百兆 郭丽萍 XING Ruijiang;ZHANG Baizhao;GUO Liping(Huadian Electric Power Research Institute Co.,Ltd.,Hangzhou 310030,China;Huadian Laizhou Power Generation Co.,Ltd.,Yantai 261414,China;Hangzhou Jinjiang Group Co.,Ltd.,Hangzhou 310000,China)

机构地区:[1]华电电力科学研究院有限公司,浙江杭州310030 [2]华电莱州发电有限公司,山东烟台261414 [3]杭州锦江集团有限公司,浙江杭州310000

出  处:《电工技术》2024年第1期160-162,179,共4页Electric Engineering

摘  要:主变复压过流保护是电厂主变相间后备保护的标配。长期以来,由于该保护十分常用,原理简单明了,因此继电保护人员常在整定计算过程中直接给出经验值,不去校验保护的灵敏度,导致某些变压器的灵敏度不满足标准要求,造成保护不能快速、及时、准确地动作,严重威胁变压器主设备的运行安全。通过一起主变复压过流保护的电压整定案例,阐述了某些情况下低电压灵敏度不满足要求的现象,提出解决问题的措施,完善了保护方案,修正了保护的定值,使保护能更有效、快速、准确地切除故障,保护电气主设备,以便更好地服务于发电企业的安全生产工作。The complex voltage overcurrent protection is a standard configuration for inter-phase backup protection of main transformers in power plants.For a long time,due to the common use of this protection and its simple and clear principle,relay protection personnel have been prone to laziness,negligence,and carelessness in the setting calculation process.They directly provide empirical values rather than check and recalculate sensitivity of the protection.This results in substandard sensitivity of some transformers and consequently incompetence of protection mechanisms in promptness and accuracy,seriously threatening operational safety of transformer main equipment.This paper reveals the phenomenon of inadequate sensitivity in some cases through a voltage setting case of complex voltage overcurrent protection,proposes measures to solve the problem,perfects the protection scheme,corrects the protection setting,and enables the protection to more effectively,quickly and accurately island faults and protect electrical main equipment.

关 键 词:电厂 主变 复合电压 过流 保护 灵敏度 

分 类 号:TM588.1[电气工程—电器]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象