不同运维方式下空气源热泵机组供暖运行耗电量分析  

Analysis of Power Consumption of Air Source Heat Pump Under Different Maintenance Modes

在线阅读下载全文

作  者:单美群 Shan Meiqun

机构地区:[1]山东电力建设第一工程有限公司

出  处:《洁净与空调技术》2024年第1期94-95,98,共3页Contamination Control & Air-Conditioning Technology

摘  要:对比不同运维方式下,济南地区办公建筑采用空气源热泵机组供暖的运行费用,得出自主运维的方式,室内温度22℃,机组冬季供暖耗电量28.4kWh/m^(2),合同能源管理的方式,室内温度20℃,机组冬季供暖耗电量15.5kWh/m^(2)。合同能源管理的方式在降低大楼耗电量的同时牺牲一定的室内舒适度。This paper compares the operating costs of air source heat pump used for heating in office buildings in Jinan area under different operation and maintenance modes,and concludes that when the indoor temperature is 22℃,the heating power consumption in winter is 28.4 kWh/m^(2)under the independent maintenance mode with indoor temperature 22℃,and the heating power consumption is 15.5 kWh/m^(2)under the energy management contract mode with indoor temperature 20C.The energy management contract mode reduces the building's power consumption while sacrificing some indoor comfort.

关 键 词:空气源热泵机组 自主运维 合同能源管理 供暖耗电量 

分 类 号:TU832[建筑科学—供热、供燃气、通风及空调工程]

 