变压器铁心多点接地导致高温过热故障分析  被引量:2

Research on High Temperature Overheat Fault Caused by Multi-point Grounding of Transformer Core

在线阅读下载全文

作  者:胡进 宋玉锋 余霖 范永存 袁胜旭 游书均 HU Jin;SONG Yufeng;YU Lin;FAN Yongcun;YUAN Shengxu;YOU Shujun(Zhaotong Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Zhaotong 657000,China;Electric Power Research Institute,Yunnan Power Grid Co.,Ltd.,Kunming 650000,China)

机构地区:[1]云南电网有限责任公司昭通供电局,云南昭通657000 [2]云南电网有限责任公司电力科学研究院,云南昆明650000

出  处:《变压器》2024年第4期67-70,共4页Transformer

摘  要:绝缘油中特征气体对于发现变压器潜伏性故障具有重要意义。本文通过油色谱分析发现了一起变压器过热故障,进而结合电气试验,验证变压器内部存在过热故障。依据油色谱和铁心对地绝缘电阻的结果,进行了变压器吊芯大修,确定故障原因为施工过程中遗留异物引起铁心多点接地造成高温过热,避免了故障的进一步发展及扩大。对此类型故障进行了理论分析和经验总结,能够有效的减少变压器的故障率。The characteristic gas in insulating oil is very important to discover the latent fault of transformer.In this paper,a transformer overheating fault is found by oil chro matography analysis,and then combined with the electrical test,it is verified that there is overheating fault in the transformer.Based on the results of oil chromatogram and in sulation resistance of iron core to Earth,the overhaul of transformer suspended core was carried out,which can avoid the further development of the fault and the occur rence of the accident.The theoretical analysis and experience summary of this type of fault are made,which accumulate experience for the safe operation and maintenance of the transformer and technical supervision in the future.

关 键 词:变压器 铁心接地 高温过热 

分 类 号:TM406[电气工程—电器]

 