检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:鲁海亮[1] 王会武 李志忠 谭波 李伟 李元杰 LU Hailiang;WANG Huiwu;LI Zhizhong;TAN Bo;LI Wei;LI Yuanjie(School of Electrical Engineering and Automation,Wuhan University,Wuhan 430072,China;Power Research Institute of State Grid Shaanxi Electric Power Company Limited,Xi’an 710100,China;China Electric Power Research Institute,Wuhan 430074,China)
机构地区:[1]武汉大学电气与自动化学院,武汉430072 [2]国网陕西省电力有限公司电力科学研究院,西安710100 [3]中国电力科学研究院有限公司,武汉430074
出 处:《高电压技术》2024年第4期1499-1507,共9页High Voltage Engineering
基 金:国家电网有限公司总部科技项目(5500-202132115A-0-0-00)。
摘 要:随着电网容量变大和新型电力系统的发展,站用10 kV系统中性点接地方式发生改变,仍沿用系统中性点不接地方式下避雷器耐受接地网地电位(U_(GPR))升高的安全限值可能会导致避雷器在其他接地方式下出现安全事故。采用电磁暂态程序ATP-draw可以搭建不同中性点接地方式下U_(GPR)反击避雷器的模型,通过校核避雷器在U_(GPR)作用下动作过程中的吸收能量,得到了中性点接地方式对避雷器耐受U_(GPR)安全限值的影响规律:中性点不接地时,避雷器耐受U_(GPR)安全限值为10~23 kV,随线路对地电容变大而减小;中性点经消弧线圈接地时,U_(GPR)在消弧线圈和线路对地电容的串联回路中产生振荡,导致避雷器耐受U_(GPR)安全限值更低,安全限值主要由脱谐度与阻尼率决定,典型值为8~9.5 kV;中性点经电阻接地时,U_(GPR)大部分耦合至高压母线,使避雷器耐受U_(GPR)安全限值更高,并随线路对地电容和中性点电阻的增大而减小,大电阻接地工况下的典型值大于15 kV,小电阻接地工况下的典型值大于25 kV。With the increase of grid capacity and the development of new power systems,the neutral grounding mode of the 10 kV station system has changed.The ground potential rise(U_(GPR))safety limit of the arrester’s tolerance under the neutral ungrounded system may lead to safety accidents of the arrester under other grounding modes.The electromagnetic transient program ATP-draw can be used to build the model of U_(GPR)counterattack arrester under different neutral grounding modes.By checking the energy absorbed by the arrester under the action of U_(GPR),the influence of neutral grounding mode on the safety limit of the arrester’s tolerance to U_(GPR)is obtained as follows:Under the neutral ungrounded system,the U_(GPR)safety limit of the arrester is 10~23 kV,which decreases with the increase of the line capacitance to the ground.Under the neutral grounding via arc suppression coil system,U_(GPR)oscillates in the series circuit of the arc suppression coil and the line’s capacitance to the ground,resulting in a lower safety limit of the arrester to withstand U_(GPR).The safety limit is mainly determined by the out-of-resonance degree and damping rate,and the typical value is 8~9.5 kV.Under the neutral grounding via resistance system,most of the U_(GPR)is coupled to the high voltage bus,so that the safety limit of the arrester to withstand U_(GPR)is higher,which decreases with the increase of the line capacitance to the ground and the neutral resistance.The typical value of the high resistance grounding condition is greater than 15 kV,and the typical value of the low resistance grounding condition is greater than 25 kV.
关 键 词:地电位升 安全限值 避雷器 中性点接地方式 反击 站用电系统
分 类 号:TM862[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.219.203.214