电缆终端头绝缘缺陷对干式高压计量装置的影响分析及预防措施  

Analysis of Influence of Insulation Fault of Cable Terminal on 10 kV Outdoor Dry-type High-Voltage Metering Device

在线阅读下载全文

作  者:周宁 斯荣 王纪东 黄乔林 李响军 ZHOU Ning;SI Rong;WANG Jidong;HUANG Qiaolin;LI Xiangjun(Shenzhen Power Supply Bureau Co.,Ltd.,Shenzhen 518100,China)

机构地区:[1]深圳供电局有限公司,广东深圳518000

出  处:《电工技术》2024年第8期210-213,共4页Electric Engineering

摘  要:针对一起新装10 kV户外干式高压计量装置运行不到10 min的爆炸事故,从计量装置后端设备类型入手,结合电缆试验数据,由表及里地剖析造成计量装置爆炸的根本原因。确定原因是后端电缆热缩终端头放电致电压互感器发生谐振,最终失控爆炸。描述了故障发生前后的表象及现场值班员对事故处理的情况,并根据引起故障的原因提出一些装置改进建议。This paper reports an explosion accident which happened in 10 minutes after the installation of a 10 kV outdoor dry-type high-voltage metering device.By combining different types of back-end equipment of the metering device with cable test data,and analysis from appearance to essence,it determines the cause of the explosion as back-end heat shrinkage-induced terminal charging which leads to resonance of voltage transformer and ultimately to explosion.It also outlines the handling of the accident by on-site attendant,and proposes some suggestions of countermeasures.

关 键 词:10 kV户外干式高压计量装置 爆炸 电压互感器 局部放电 串联谐振 

分 类 号:TM757[电气工程—电力系统及自动化]

 