某柔性直流换流站电阻器电阻值数据异常分析  

Analysis of Abnormal Resistance Data of Resistors in a VSC-HVDC Converter Station

在线阅读下载全文

作  者:王婷乐 高强 毕小鹏 WANG Tingle;GAO Qiang;BI Xiaopeng(Electric Transmission and Transformation Engineering Co.,Ltd.of Anhui,Hefei 230000,China)

机构地区:[1]安徽送变电工程有限公司,安徽合肥230000

出  处:《电工技术》2024年第9期177-178,197,共3页Electric Engineering

摘  要:针对某柔性直流换流站年度检修期间连续检测出电阻器异常问题进行分析。通过现场拆解,发现设备结构存在隐患,提出电阻器包边结构和安装工艺优化整改措施。检测结果显示优化措施是可行的、有效的,有力保障了设备运行安全,也为今后类似问题提供参考。This paper reports an analysis on the continuous detection of abnormal resistors during the annual maintenance period of a flexible DC converter station.Through on-site disassembly,it was found that there were hidden dangers in the equipment structure.Measures for optimizing and rectifying resistor edge structure and installation process were proposed.After two years of tracking and testing comparison,the results have showed that the optimization measures are feasible and effective,effectively ensuring safety of equipment operation and providing reference for coping with similar problems.

关 键 词:柔性直流 换流站 电阻器 

分 类 号:TM721[电气工程—电力系统及自动化]

 