自动电压控制参数误整定引起发电机功率振荡原因分析  

Analysis of generator power oscillation caused by missetting of automatic voltage control parameters

在线阅读下载全文

作  者:黄康 唐潇潇 HUANG Kang;TANG Xiaoxiao(State Grid Sichuan Integrated Energy Service Co.,Ltd.,Chengdu 610041,China)

机构地区:[1]国网四川综合能源服务有限公司,四川成都610041

出  处:《电气应用》2024年第6期31-35,共5页Electrotechnical Application

摘  要:电厂侧自动电压控制系统对改善高压侧电压水平具有重要作用,但其参数误整定将严重威胁发电机组的安全稳定运行。针对一起自动电压控制系统参数误整定引起的水电机组功率振荡事件,阐述了自动电压控制和低励限制的基本原理,详细分析了子站参数误整定导致功率振荡事件的原因,并提出了针对性的防范解决措施。The automatic voltage control system on the power plant side plays an important role in improving the voltage level of the high-voltage side,but its parameter missetting will seriously threaten the safe and stable operation of the generator.This paper elaborates on the basic principles of automatic voltage control and under excitation limiter in response to a power oscillation event caused by incorrect setting of automatic voltage control system parameters in hydropower units.The reasons for power oscillation events caused by incorrect setting of slave station parameters are analyzed in detail,and targeted preventive measures and solutions are proposed.

关 键 词:自动电压控制 低励限制 功率振荡 子站参数 励磁系统 

分 类 号:TM62[电气工程—电力系统及自动化]

 