摘 要:深入分析了现行标准对消防水泵启动控制方式的要求,阐明了消防水泵不同启动控制方式之间的关系,明确了不同消防给水系统应设置的消防水泵启动控制方式,并对可能影响消防水泵启动的有关争议问题进行了讨论,给出不必纠结于流量开关和压力开关谁应该先启动,以及流量开关的设置位置的结论。要求消防水泵控制柜应随时处于被监控状态,并对制定消防水泵控制柜产品标准提出了建议。This paper deeply analyzes the requirements of the current standard for the start control mode of the fire pump,clarifies the relationship between different start control modes of the fire pump,clarifies the start control mode of the fire pump that should be set in different fire water supply systems,and discusses the relevant controversial issues that may affect the start of the fire pump,and gives that it is not necessary to struggle with the flow switch and pressure switch who should start first,and the conclusion of the setting position of the flow switch.It is required that the fire pump control cabinet should be monitored at any time,and it is suggested to formulate the product standard of the fire pump control cabinet.