检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:郁景礼 梁冠峰 张莉珠 何健明 YU Jingli;LIANG Guanfeng;ZHANG Lizhu;HE Jianming(Foshan Power Supply Bureau of Guangdong Power Grid Co.,Ltd.,Foshan 528000,China)
机构地区:[1]广东电网有限责任公司佛山供电局,广东佛山528000
出 处:《电工技术》2024年第11期170-173,共4页Electric Engineering
摘 要:变电运维人员发现电压互感器二次电压异常,及时排查并确定故障范围,执行倒闸操作方案将故障隔离并恢复完好设备运行。试验发现故障设备气室SF6气体超标,解体检查发现L2导电杆与线圈连接头烧损。为此,分析了导致异常的原因,提出了注意事项和防范措施,为避免其他变电站发生类似电压异常提供借鉴。The operation and maintenance personnel in an actual substation discovered abnormal secondary voltage of PT,promptly investigated and determined the fault range,implemented a reverse switch operation to isolate the fault and restore operation of the intact equipment.The test showed a over-limit SF 6 gas content in the gas chamber of the faulty equipment,and the disassembly inspection found that the L2 conductor rod and coil connection head were burned.The reasons for the anomaly have then been analyzed,and precautions and preventive measures have been proposed,which may contain useful information for avoiding similar faults.
关 键 词:电压互感器 二次电压异常 倒闸操作 接头烧损 预控措施
分 类 号:TM732[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7