基于NaErF_(4)@NaYF_(4)上转换材料的高灵敏度变电站设备温度监测  被引量:2

High Precision Temperature Monitoring of Substation Equipment Based on NaErF_(4)@NaYF_(4) Upconversion Material

在线阅读下载全文

作  者:杨帆 张利 李楚涵 陈铭岳 马致臻 YANG Fan;ZHANG Li;LI Chuhan;CHEN Mingyue;MA Zhizhen(Beijing Electric Power Economic Research Institute,Beijing 100055,China;State Grid Beijing Electric Power Company,Beijing 100055,China)

机构地区:[1]北京电力经济技术研究院有限公司,北京100055 [2]国网北京城区供电公司,北京100055

出  处:《人工晶体学报》2024年第8期1434-1442,共9页Journal of Synthetic Crystals

基  金:北京电力经济技术研究院有限公司科技项目(SGBJJY00SJJS2100388)。

摘  要:实时监测变电站设备的温度变化,预防故障,对保障电力供应至关重要。目前,变电站设备的温度监测主要依赖人工红外测温技术,存在操作依赖性强、易受干扰等问题,且难以检测设备内部故障。发光强度比(LIR)是一种不受光谱损失、环境等因素影响的稳定光学参数,适用于温度检测。稀土掺杂的上转换(UC)材料的多发射峰特性与LIR技术高度契合,展现出在高精度温度监测方面的潜力。本文提出了一种基于NaErF_(4)@NaYF_(4)核壳结构的UC材料和LIR技术的非接触式变电站设备温度监测方法。实验表明,该方法在25~225℃具有高准确性和灵敏度,灵敏度高达35×10^(-3)℃^(-1),可有效监测设备内外的温度变化,为变电站设备的温度监测提供了新的技术方案。Real-time monitoring of temperature changes in substation equipment is crucial for preventing failures and ensuring a stable power supply.Currently,temperature monitoring of substation equipment primarily relies on manual infrared thermometry,which has limitations such as strong operational dependence,susceptibility to interference,and difficulty in detecting internal faults.The luminous intensity ratio(LIR) is a stable optical parameter unaffected by factors such as spectral loss and environmental influences,making it suitable for temperature detection.The multi-emission characteristics of rare-earth-doped upconversion(UC) materials are highly compatible with LIR technology,demonstrating their potential in high-precision temperature monitoring.Here we introduces a non-contact temperature monitoring method for substation equipment based on NaErF_(4)@NaYF_(4) core-shell UC materials and LIR technique.Experiments show that the method has high accuracy and sensitivity within temperature range of 25 ℃ to 225 ℃,with a sensitivity as high as 35×10^(-3) ℃^(-1),effectively monitoring temperature changes both inside and outside the equipment.This provides a new technical solution for temperature monitoring of substation equipment.

关 键 词:变电站 温度监测 上转换发光 发光强度比 核壳结构 NaErF_(4)@NaYF_(4) 

分 类 号:O734[理学—晶体学] TM63[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象