作 者:王小帅 薛永端[1] 刘萃萃 田君杨 徐丙垠[3] WANG Xiaoshuai;XUE Yongduan;LIU Cuicui;TIAN Junyang;XU Bingyin(College of New Energy,China University of Petroleum(East China),Qingdao 266580,China;Power Dispatching Control Center of Guangxi Power Grid,Nanning 530023,China;Research Center for Smart Grid,Shandong University of Technology,Zibo 255049,China)
机构地区:[1]中国石油大学(华东)新能源学院,山东省青岛市266580 [2]广西电网电力调度控制中心,广西壮族自治区南宁市530023 [3]山东理工大学智能电网研究院,山东省淄博市255049
出 处:《电力系统自动化》2024年第16期174-183,共10页Automation of Electric Power Systems
基 金:国家自然科学基金资助项目(52077221)。
摘 要:灵活接地系统发生高阻接地故障时,中性点小电阻并联阶段保护往往拒动,仍需考虑小电阻退出时的暂态特征对已有暂态故障选线方法的影响。并联小电阻退出时伴随一定的暂态过渡过程,文中针对此过程建立灵活接地系统单相接地故障暂态等值电路。分析了并联小电阻退出时系统各暂态电气量特征、不同故障情况对暂态电气量幅值的影响、暂态零序电流与暂态零序电压的约束关系,明确并联小电阻退出后暂态量对暂态故障选线方法稳定性的影响。当灵活接地系统高阻接地故障小电阻退出时,产生的暂态电气量将导致暂态幅值比较法、暂态极性选线法、暂态功率方向法误动,但暂态零序电流投影法选线正确,仿真验证了分析结果的正确性。When a high-resistor grounding fault occurs in a flexible grounding system,the protection during the parallel stage of neutral point small resistor often refuses to activate,so it is still necessary to consider the impact of the transient characteristics of small resistor exit on the existing transient faulty-line selection methods.The exit of the parallel small resistor is accompanied by a certain transient transition process.For this process,a transient equivalent circuit for a single-phase grounding fault in a flexible grounding system is established.The characteristics of transient electrical quantities of the system when the parallel small resistor exits,the impact of different fault conditions on the amplitude of transient electrical quantities,and the constraint relationship between transient zero-sequence current and transient zero-sequence voltage are analyzed.The impact of transient quantities after the parallel small resistor exits on the stability of the transient faulty-line selection methods is clarified.When the small resistor exits during a high-resistor grounding fault in a flexible grounding system,the generated transient electrical quantities will cause misoperation in the transient amplitude comparison method,transient polarity selection method,and transient power direction method,but the transient zero-sequence current projection method for the line selection is correct.The simulation verifies the accuracy of the results.
关 键 词:灵活接地系统 单相接地故障 暂态故障特征 故障选线
分 类 号:TM862[电气工程—高电压与绝缘技术]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.144.97.63