检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:刘洋[1] 何柏娜[1] 吴硕 孟凡涛 林莘[2] 代维汉 尉元龙 王硕 张东进 LIU Yang;HE Bai-na;WU Shuo;MENG Fan-tao;LIN Xin;DAI Wei-han;WEI Yuan-long;WANG Shuo;ZHANG Dong-jin(College of Electrical and Electronic Engineering,Shandong University of Technology,Zibo 255049,China;Key Laboratory of Special Machine and High Voltage Apparatus,Ministry of Education,Shenyang University of Technology,Shenyang 110870,China)
机构地区:[1]山东理工大学电气与电子工程学院,淄博255049 [2]沈阳工业大学特种电机与高压电器教育部重点实验室,沈阳110870
出 处:《科学技术与工程》2024年第22期9437-9444,共8页Science Technology and Engineering
基 金:山东省自然科学基金(ZR2021ME057);特种电机与高压电器教育部重点实验室开放课题(KFKT202111);山东省研究生教育质量提升计划项目(SDYAL2022114)。
摘 要:为提高系统运行稳定性,高补偿度串补装置广泛投入使用,但线路故障后潜供电流存在高幅值的低频分量,潜供电弧难以自熄。针对此问题,基于交直流混联输电线路,研究了不同布置方式下串补度对潜供电流与恢复电压幅值影响,提出了一种固定串补(fixed series compensation,FSC)和可控串补(thyristor controlled series compensation,TCSC)混合复用抑制潜供电弧的方法。此外,为满足线路对高补偿度的需求,设计FSC和TCSC混合复用串补度最佳配置方案。结果表明,交直流混联线路采用串补度40%的双平台分散布置方式,潜供电流与恢复电压幅值达到最小,燃弧时间最短。高补偿度串补线路TCSC采用串补度10%、20%的配置方案更利于熄弧,提高重合闸成功率。In order to improve the stability of system operation,high compensation series compensation devices have been widely used.However,after a line fault,there are low-frequency components with high amplitude in the secondary arc current,making it difficult for the secondary arc to self extinguish.In response to this issue,the impact of series compensation on the amplitude of secondary arc current and recovery voltage were studied under different arrangements of AC/DC hybrid transmission lines,and a method of FSC and TCSC hybrid multiplexing was proposed to suppress secondary arc in this article.In addition,to meet the demand for high compensation degree in the line,the optimal configuration scheme for series compensation degree was designed with FSC and TCSC mixed multiplexing.The results show that a series compensation degree of 40%in a dual platform decentralized layout in the AC/DC hybrid transmission line,the minimum amplitude of the secondary arc current and recovery voltage are realized,and the shortest arcing time is also realized.In high compensation series compensation lines,when a configuration scheme with series compensation of 10%and 20%in the TCSC,it is more conducive to arc extinguishing and the success rate of reclosing.
关 键 词:交直流混联输电线路 FSC和TCSC混合复用 潜供电弧 串补度配置方案设计
分 类 号:TM930[电气工程—电力电子与电力传动]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7