某核电厂消防水管道腐蚀原因分析  

Corrosion Analysis of Fire Water Pipeline in a Nuclear Power Plant

在线阅读下载全文

作  者:姚旭京 刘洪群[2] YAO Xu-jing;LIU Hong-qun(CNNC Nuclear Power Operations Management Co.,Ltd.Jiaxing 314000,China;Suzhou Nuclear Power Research Institute,Suzhou 215004,China)

机构地区:[1]中核核电运行管理有限公司,浙江嘉兴314000 [2]苏州热工研究院有限公司,江苏苏州215004

出  处:《全面腐蚀控制》2024年第7期192-194,共3页Total Corrosion Control

摘  要:某核电厂常规岛喷水灭火系统的消防喷淋管道频繁发生腐蚀穿孔。本文从消防喷淋管道的运行环境、定期试验规程、防腐措施、腐蚀形貌特点等方面开展了系统分析。结果表明,采用内外镀锌防腐措施的消防喷淋管道设计为内部通空气的预作用灭火系统,在开展定期试验后,部分水平布置的管道留有残水,在含氧条件下发生腐蚀穿孔。The fire sprinkler pipes of the conventional island sprinkler system of a nuclear power plant frequently suffer from corrosion and perforation.This article systematically analyzes the operating environment,regular testing procedures,anti-corrosion measures,and corrosion morphology characteristics of fire sprinkler pipelines.On the surface of the results,the fire sprinkler pipeline designed with internal and external galvanized anti-corrosion measures is a pre action fire extinguishing system with internal air circulation.After conducting regular tests,some horizontally arranged pipelines have residual water,which causes corrosion perforation under oxygen-containing conditions.

关 键 词:核电厂 消防水管道 镀锌层 腐蚀穿孔 

分 类 号:TG174[金属学及工艺—金属表面处理]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象