某电厂高压加热器电动门跳闸保护逻辑优化  

Logic Optimization of Tripping Protection for High Pressure Heater Electric Door in Power Plant

在线阅读下载全文

作  者:吴向军 陈巍 张志 崔宇 WU Xiangjun;CHEN Wei;ZHANG Zhi;CUI Yu(Liaoning Huadian Tieling Power Generation Co.,Ltd.,Tieling,Liaoning 112606,China;Huadian Liaoning Energy Development Co.,Ltd.,Shenyang,Liaoning 110102,China;Tieling Open University,Tieling,Liaoning 112004,China)

机构地区:[1]辽宁华电铁岭发电有限公司,辽宁铁岭112606 [2]华电辽宁能源发展股份有限公司,辽宁沈阳110102 [3]铁岭开放大学,辽宁铁岭112004

出  处:《东北电力技术》2024年第7期46-50,共5页Northeast Electric Power Technology

摘  要:针对某电厂5号、6号机组高压加热器电动门保护逻辑存在的安全隐患,提出“3取2”的动作逻辑条件,设计安装电动门阀位确认装置,优化逻辑并进行试验。结果表明,改进后的逻辑可有效防止高压加热器电动门误动导致的高压加热器受损事故,延长其使用寿命,保证机组安全稳定运行。According to the protection logic of No.5 and No.6 units high pressure heater electric door in a power plant having the potential safety hazard,it proposes the“two out of three”action logic condition,and designs and installs electric door and valve position confirmation device,which optimizes the logic and has experiment.The results show that the improved logic can prevent the damage accident of high pressure heater caused by the wrong operation of high voltage electric door,and extends its service life,which ensures the safe and stable operation of the unit.

关 键 词:高压加热器 电动执行机构 逻辑优化 

分 类 号:TM621[电气工程—电力系统及自动化]

 