摘 要:为研究主动式冷梁(ACB)在船舶舱室的热舒适性,基于某船舶舱室环境,采用实验方法对不同送风参数下的船舶舱室ACB空调热舒适性进行研究,并与传统的风机盘管(FCU)空调进行对比。实验结果表明,送风温度、送风量和送风角度分别增加时,室内热舒适性均呈现先升高后下降的趋势。送风温度、送风量和送风角度为20℃、80 m3/h、120°,室内的热舒适性均达到最佳。同时相较于基准工况,送风温度能降低PMV-PPD绝对值50%和10%;送风量可以降低了60%的人员竖直空气温差(VATD),75%和77.4%的PMV-PPD绝对值,提高了9.6%的空气分布特性指标(ADPI);送风角度可以分别降低20%的人员VATD、55.5%和54.5%的PMV-PPD绝对值,提高9.8%的ADPI。此外,ACB的室内热环境参数比FCU更平稳,人员VATD降低了1.5℃,热舒适性更高。In order to study the thermal comfort of active chilled beam(ACB)in ship cabins,based on a certain ship cabin environment,experimental methods were used to study the thermal comfort of ACB air conditioning in ship cabins un-der different air supply parameters,and compared with traditional fan coil units(FCU)air conditioner for comparison.The experimental results show that when the air supply temperature,air supply volume and air supply angle increase respectively,the indoor thermal comfort first increases and then decreases.The air supply temperature,air volume and air supply angle are 20°C,80 m/h,and 120°,and the indoor thermal comfort is optimal.At the same time,compared with the baseline working conditions,the supply air temperature can reduce the absolute value of PMV-PPD by 50%and 10%;the air supply volume can reduce the personnel vertical air temperature difference(VATD)by 60%,and the PMV-PPD by 75%and 77.4%.The ab-solute value of PPD improves the air distribution characteristic index(ADPI)by 9.6%;the air supply angle can reduce the personnel VATD by 20%,the absolute value of PMV-PPD by 55.5%and 54.5%respectively,and improve the ADPI by 9.8%.In addition,ACB The indoor thermal environment parameters are more stable than those of FCU,personnel VATD is reduced by 1.5℃,andthermal comfortishigher.
分 类 号:U664.86[交通运输工程—船舶及航道工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49