检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:姜君 王增平[1] 王彤[1] 吴英姿 冀肖彤 夏勇军 JIANG Jun;WANG Zengping;WANG Tong;WU Yingzi;JI Xiaotong;XIA Yongjun(School of Electrical and Electronic Engineering,North China Electric Power University,Beijing 102206,China;Power Research Institute of State Grid Hubei Electric Power Co.,Ltd,Wuhan 430000,China)
机构地区:[1]华北电力大学电气与电子工程学院,北京102206 [2]国网湖北省电力有限公司电力科学研究院,湖北武汉430000
出 处:《华北电力大学学报(自然科学版)》2024年第5期45-55,I0006,共12页Journal of North China Electric Power University:Natural Science Edition
基 金:国家电网公司总部科技项目(4000-202222070A-1-1-ZN).
摘 要:电网电压跌落时能够向系统提供无功支撑是对并网风电机组的基本要求。风电机组无功支撑对故障电流有着直接影响,可能使集电线电流速断保护灵敏度下降,同时可能使保护失去选择性。文章首先根据双馈异步电机(double feed induction generator,DFIG)数学模型及无功电流支撑原理,分析了浅、深度故障运行下DFIG分别通过转子侧变流器(rotor-side converter,RSC)与网侧变流器(grid-side converter,GSC)调节输出无功对故障电流的影响。针对DFIG无功优先控制可能造成集电线电流速断保护灵敏度降低以及其与箱变熔断器失去配合的问题,提出了在DFIG无功优先控制计算整定初值基础上根据集电线电压跌落程度附加自适性补偿量的定值调整方法。通过仿真验证,表明整定值改进后能够在保证全线速动的前提下大幅提升保护的选择能力。It is a basic requirement for grid connected wind turbines to provide reactive power support to the system when the grid voltage drops.The reactive power support of wind turbine has a direct impact on the fault current,which may reduce the sensitivity of the current quick break protection of the collector line,and may also make the protection lose its selectivity.Firstly,based on the mathematical model of DFIG(double feed induction generator)and the principle of reactive current support,we analyzed the influence of DFIG regulating output reactive power on fault current through rotor side converter(RSC)and grid side converter(GSC)respectively under shallow and deep fault operation.Aiming at the problem that DFIG reactive power priority control may reduce the current quick break protection sensitivity of the collector line and lose coordination with the box transformer fuse,we proposed a set value adjustment method based on DFIG reactive power priority control calculation of the initial setting value and additional adaptive compensation according to the collector line voltage sag.The simulation results show that the improved setting value can greatly improve the selection ability of protection on the premise of ensuring the rapid operation of the whole line.
关 键 词:继电保护 无功优先 双馈异步电机 电网故障 变流器 集电线 箱变熔断器
分 类 号:TM773[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7