DC75kV高压电缆头故障分析与对策  

Analysis and Countermeasures of DC75kV High Voltage Cable Head Fault

在线阅读下载全文

作  者:刘才斌 LIU Cai-bin(Southwest Copper Branch of Yunnan Copper Industry Co.,Ltd.,Kunming 650102,China)

机构地区:[1]云南铜业股份有限公司西南铜业分公司,云南昆明650102

出  处:《世界有色金属》2024年第18期220-222,共3页World Nonferrous Metals

摘  要:为确定电收尘75kV交联聚乙烯绝缘直流高压电缆终端头闪烙事故的原因,通过对事故电缆终端头检查、分析,认为电缆终端头安装不符合要求是电缆终端头被击穿的主要原因,重点阐述了DC75kV高压电缆头制作工艺,提出了预防同类事故发生的相关对策。In order to determine the cause of the flashover accident of 75kV cross-linked polyethylene insulated DC high-voltage cable terminal with electrostatic precipitator,through inspection and analysis of the accident cable terminal,it is considered that the main reason for the breakdown of the cable terminal is that the installation of the cable terminal does not meet the requirements.T he treatment process of DC 75kV high-voltage cable head is emphasized,and relevant countermeasures to prevent similar accidents are proposed.

关 键 词:DC75kV 交联聚乙烯电缆 电缆终端头 闪烙 事故分析 

分 类 号:TM75[电气工程—电力系统及自动化]

 