作 者:杨旗 喻磊 郑友卓 何昊晨 李跃 林心昊 黄伟 徐敏 YANG Qi;YU Lei;ZHENG Youzhuo;HE Haochen;LI Yue;LIN Xinhao;HUANG Wei;XU Min(Guizhou Power Grid Co.,Ltd.,Guiyang,Guizhou 550000,China;CSG Electric Power Research Institute Co.,Ltd.,Guangzhou,Guangdong 510663,China)
机构地区:[1]贵州电网有限责任公司,贵州贵阳550000 [2]南方电网科学研究院有限责任公司,广东广州510663
出 处:《广东电力》2024年第10期135-142,共8页Guangdong Electric Power
基 金:广东省自然科学基金面上项目(2019A1515012122);中国南方电网有限责任公司科技项目(GZKJXM20210486)。
摘 要:针对架空配电线路覆冰在线监测问题,提出一种基于超声波测距原理的架空配电线路覆冰厚度监测技术,研发超声波覆冰监测装置并分别进行实验室和现场应用检验。该方法采用超声波测距飞行时间法,计算线路覆冰前后超声探头与线路的距离,依据其差值得到线路覆冰厚度。实验室内以圆形铁棒模拟配电线路,在搭建的超声波监测配电线路试验平台条件下,当覆冰厚度检测值为16.74 mm时,其与实测值的相对误差为5.08%。超声波覆冰监测装置在贵州某配电线路挂网应用期间,能正常上传环境温度、相对湿度和测距数据,2024年2月27日15:36:52测得线路覆冰厚度值为16.76 mm,与实测值的相对误差仅4.23%。实验室和现场应用检验结果验证了所提架空配电线路覆冰超声波监测技术的有效性和准确性。In view of the problem of icing on-line monitoring of the overhead distribution lines,this paper puts forward a technology of detecting icing thickness of overhead distribution lines based on the principle of ultrasonic distance measurement,and develops an ultrasonic icing monitoring device,which is respectively applied to the laboratory and the actual distribution lines.This technology uses ultrasonic time-of-flight method to calculate the distance between the ultrasonic probe and the line before and after icing,and obtains icing thickness of the line by the difference value.In the laboratory,the round peeler is used to simulate the distribution line under the built test platform condition.The simulation results show that when the detected value of icing thickness is 16.74 mm,the relative error between the measured value and the detected is 5.08%.During the application of the ultrasonic icing monitoring device in one distribution line in Guizhou,the device can upload the ambient temperature,relative humidity and ranging data normally.The icing thickness of the line measured at 13:36:52 on February 27 in 2024 is 16.76 mm,and the relative error is only 4.23%compared with the artificial measured value.The validity and accuracy of the ultrasonic monitoring technique for icing of overhead distribution lines are verified both by laboratory and filed applications.
分 类 号:TM752.5[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.145.81.212