三相四线表单相失压时更正系数为2的原因分析  

Analysis of Correction Coefficient Being 2 with Respect to a Three-phase Four-wire Meter Encountering Single-phase Voltage Loss

在线阅读下载全文

作  者:邓得政 DENG Dezheng(State Grid Tianjin Dongli Company,Tianjin 300300,China)

机构地区:[1]国网天津东丽公司,天津300300

出  处:《电工技术》2024年第19期125-126,130,共3页Electric Engineering

摘  要:针对三相四线表出现单相失压而更正系数为2的情况进行了现场检查与分析,发现A相、零相电压线熔断导致计量二元件和计量三元件计量电压为线电压分压电压是造成表计失压且更正系数为2的原因。This essay focuses on a situation of correction coefficient being 2 with respect to a three-phase four-wire meter encountering single-phase voltage loss.It reports the on-site inspection and analysis carried out,which found that the fusion of A-phase and zero-phase voltage lines made the measured voltages from the second and the third measuring elements actually partial voltage of the line,and consequently resulted in the aforementioned situation.

关 键 词:三相四线表 单相失压 更正系数 

分 类 号:TM933[电气工程—电力电子与电力传动]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象