作 者:LI Yaohong WANG Pengxiang PENG Bin BIAN Xiaoyang
出 处:《Journal of Thermal Science》2024年第6期2203-2220,共18页热科学学报(英文版)
基 金:supported by the National Natural Science Foundation of China(No.51966009);the Key Research and Development Program of Gansu Province(NO.20YF8GA057).
摘 要:The important indications for assessing CCHP(combined cooling,heating and power)systems are their supply-demand matching characteristics between the user demand side and the energy supply side.These characteristics are primarily influenced by different building types and operating strategies.In view of the energy redundancy of the following electric load(FEL)and following thermal load(FTL)operation strategies and the energy deficiency of the following hybrid electric-heating load(FHL)operation strategy,this paper proposes an improved following balanced heat-electrical load(IFBL)operation strategy based on the following balanced heat-electrical load(FBL)operation strategy.Based on the energy utilization rate as the objective function,this paper optimizes the installed capacity of CCHP systems in different buildings and proposes an energy factor for evaluating the supply-demand matching characteristics of the system.The results show that the energy utilization rate and energy factor of the system under IFBL are optimal relative to the other operation strategies.Secondly,the hotel building has the highest energy utilization rate and the lowest energy factor;on the contrary,the office building has the lowest energy utilization rate and the highest energy factor.Finally,the analysis of supply-demand matching for different building types under multiple operating strategies shows that the hospital and hotel systems exhibit optimal supply-demand matching performance under the IFBL strategy,with values of 0.945 and 0.938,respectively;on the contrary,the office system has an optimal supply-demand matching of 0.935 under the FEL strategy.Under the FTL strategy,the systems of all three buildings exhibit poor matching performance.
关 键 词:combined cooling heating and power system(CCHP) operation strategy energy utilization energyfactor matching supply and demand
分 类 号:TM61[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:3.137.198.25