检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:江金洋 张相杰 尹心 程晓 陈涛 杨帆[2] JIANG Jinyang;ZHANG Xiangjie;YIN Xin;CHENG Xiao;CHEN Tao;YANG Fan(State Grid Chongqing Electric Power Research Institute,Chongqing 400015,China;State Key Laboratory of Power Transmission Equipment&System Security and New Technology,Chongqing University,Chongqing 400044,China)
机构地区:[1]国网重庆市电力公司电力科学研究院,重庆400015 [2]重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆400044
出 处:《高压电器》2024年第11期147-153,共7页High Voltage Apparatus
基 金:国网公司科技项目(SGCQDK00NYJS000063)。
摘 要:为明确气体绝缘开关设备(gas insulated switchgear,GIS)开关操作过程中的电磁暂态特性。在某750 kV气体绝缘变电站投运期间,设计了测量方案对隔离开关单次闭合、断路器单次闭合两类操作下的瞬态外壳电压(transient enclosure voltage,TEV)与暂态地电位升高(transient ground potential rise,TGPR)进行了测量,并对两类操作的测量结果从宏脉冲和微脉冲特性方面进行了对比分析。结果表明:TEV和TGPR的最大值分别为22.8 kV和19.6 kV,在许多测点处TGPR均高于TEV;相比于断路器合闸操作,隔离开关合闸操作产生的电磁振荡能量小,但宏脉冲持续时间长、击穿次数多。For clarifying the electromagnetic transient characteristics during the switching operation of gas insulated switchgear(GIS),the measurement scheme is designed to measure the transient enclosure voltage(TEV)and the transient ground potential rise(TGPR)under such two types of operations as single close operation of disconnector and circuit breaker during the operation of one 750 kV GIS.And the measurement results of the two types of operations are compared and analyzed from the macro-pulse and micro-pulse characteristics aspects.The results show that the maximum values of TEV and TGPR are 22.8 kV and 19.6 kV,respectively,and TGPR is higher than TEV at many measuring points.Compared to the closed operation of circuit breaker,the electromagnetic oscillation energy generated by the closed operation of disconnector is small,but the duration of macro pulse is long and number of breakdown is more.
分 类 号:TM63[电气工程—电力系统及自动化] TM712
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:18.217.252.20