检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:许宗金 邹思 罗灿 杨雪斌 Xu Zongjin;Zou Si;Luo Can;Yang Xuebin(Guangdong Shenling Environmental System Co.,Ltd.)
机构地区:[1]广东申菱环境系统股份有限公司
出 处:《制冷与空调》2024年第11期22-28,共7页Refrigeration and Air-Conditioning
摘 要:对北京地区某数据中心空调系统能效进行全年动态模拟计算,分析系统实际冷负荷率及冷水机组能效对系统能效的影响。结果表明:采用冷水机组A时,空调系统在负荷率100%下全年平均设计能效比为9.61,远低于负荷率70%时全年平均设计能效比;在负荷率70%下,与采用冷水机组A相比,采用与其具有相同制冷量但不同COP的冷水机组B时,空调系统全年平均设计能效比提升0.54。A year-round dynamic simulation is conducted on the energy efficiency of the air-conditioning system of a data center in Beijing.The influence of actual cooling load ratio and energy efficiency of the water chiller on the system energy efficiency is analy-zed.The results show that when utilizing water chiller A,the air-conditioning system obtains an annual average design energy efficiency ratio(EER)of 9.61 at 100%load ratio,which is much lower than the EER achieved at 70%load ratio.At 70%load ratio,the use of water chiller B,which has the same cooling capacity but a different coefficient of performance(COP),results in an increase of 0.54 in the annual average design EER of the air-conditioning system,compared with using water chiller A.
分 类 号:TB6[一般工业技术—制冷工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.49