深圳地区写字楼变风量空调系统设计总结  

Design Summary of Variable Air Volume Air Conditioning System for Office Buildings in Shenzhen Area

在线阅读下载全文

作  者:贺志明[1] 周青山 HE Zhiming;ZHOU Qingshan(Hunan University,Shenzhen 518000,China;Tianjin Chengjian University,Shenzhen 518000,China)

机构地区:[1]湖南大学土木工程学院,深圳518000 [2]天津城建大学能源与安全工程学院,深圳518000

出  处:《制冷》2024年第5期84-86,共3页Refrigeration

摘  要:结合工程实例,详细介绍变风量空调系统设计过程,并统计深圳地区写字楼变风量空调系统设计案例及运行调试反馈,得出变风量空调系统组合式风柜选型建议,空调室内冷指标不宜小于120 W/m^(2),含新风冷指标不宜小于150 W/m^(2),机外静压不小于600 pa,单位空调面积送风量指标25~30 m^(3)/h/m^(2)。研究结果满足当前工作需要,对行业同类型项目有借鉴意见。Based on engineering examples,the design process of variable air volume air conditioning systems is introduced in detail,and the design cases and operation debugging feedback of variable air volume air conditioning systems in office buildings in Shenzhen are analyzed.Suggestions for the selection of combined air cabinets for variable air volume air conditioning systems are obtained.The indoor cooling index should not be less than 120W/m^(2),including fresh air cooling index should not be less than 150W/m^(2),the external static pressure should not be less than 600pa,and the air supply index per unit air conditioning area should be 25-30m^(3)/h/m^(2).The research results meet the current work needs and provide reference opinions for similar projects in the industry.

关 键 词:变风量空调系统 焓湿图 超高层写字楼 工程实例 变风量末端BOX 

分 类 号:TU831.3[建筑科学—供热、供燃气、通风及空调工程]

 