摘  要:低气压闭锁重合闸是500kV断路器保护的重要功能之一。文章以一起500 kV断路器保护低气压闭锁重合闸回路异常事件为例,从低气压闭锁重合闸回路接线、电源正负电、辅助接点三方面分析异常原因并给出了处理过程,总结了此类设备在后续运行维护工作中的排查思路和方法。The low-pressure lockout reclosure is one of the critical functions in the protection of 500 kV circuit breakers.This paper takes an abnormal event in the low-pressure lockout reclosure circuit of a 500 kV circuit breaker protection system as an example,and analyzes the causes of the abnormality from three aspects:the wiring of the low-pressure lockout reclosure circuit,power supply polarity,and auxiliary contacts.It also provides the handling process and summarizes the troubleshooting ideas and methods for such equipment in subsequent operation and maintenance work.