检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:赵杰 Zhao Jie
机构地区:[1]无锡光子芯片联合研究中心,江苏省无锡市214000
出 处:《洁净与空调技术》2024年第4期26-28,共3页Contamination Control & Air-Conditioning Technology
摘 要:电子洁净厂房的建设对洁净室系统要求较高,尤其是温度和湿度指标。以无锡某实际工程项目为案例,对该项目的冷热源系统、洁净空调系统、通风系统的设计进行了详细介绍,通过上述三个系统的协同运行,满足了洁净室百级区(温度22℃±0.25℃、湿度45%±7%)和千级区(温度22℃±1℃、湿度45%±10%)的设计要求,为后续洁净厂房的建设提供参考价值。The construction of electronic clean workshop has high requirements for clean room system,especially temperature and humidity indicators.Taking a practical engineering project in Wuxi as an example,the design of the project's cold and heat source system,clean air conditioning system and ventilation system is introduced in detail.Through the cooperative operation of the above three systems,the design requirements of the clean room thousand-level zone(temperature 22±0.25℃,humidity 45±7%)and the 100-level zone(temperature 22±1℃,humidity 45±10%)are met.It provides reference value for the subsequent construction of clean workshop.
关 键 词:洁净空调 风冷机组 新风机组 通风系统 净化等级 温度 湿度
分 类 号:TU831[建筑科学—供热、供燃气、通风及空调工程]