10 kV接地造成的开关柜过电压烧坏跳闸事件分析  

Analysis of Switchgear Overvoltage Burnout Trip Caused by 10 kV Grounding

在线阅读下载全文

作  者:吕乐 燕跃豪 孙明浩 赵振山 郭星 李锐 LYU Le;YAN Yuehao;SUN Minghao;ZHAO Zhenshan;Guo Xing;LI Rui(Zhengzhou Power Supply Company State Grid Henan Electric Power Company,Henan Zhengzhou 450006,China)

机构地区:[1]国网河南省电力公司郑州供电公司,河南郑州450006

出  处:《农村电气化》2024年第12期109-111,共3页Rural Electrification

摘  要:文章分析一起10 kV接地造成开关柜过电压跳闸事件,某10 kV馈线线路A相接地,B、C相电压升高,15板(1号电容器)因弧光过电压,母线室内相间绝缘击穿,并迅速发展为三相短路,电弧漂移造成母线室背部挡板和下挡板烧蚀,因开关柜内触头严重发热,导致绝缘件性能劣化,使柜内相间短路快速发生。This paper analyzes an overvoltage tripping event of switchgear caused by 10 kV grounding.Phase A of the 10 kV feeder line is connected to the ground,voltages of phases B and C increased,15 board(capacitor No.1)due to arc overvoltage,indoor insulation breakdown of the bus,and rapidly developed into a three-phase shortcircuit.Arcdrift caused the ablation of the back baffle of bus room and the lower baffle,serious heat in the switch cabinet contacts,resulting in insulation performance deterioration,and interphase short circuit in thr cabinet occurs quickly.

关 键 词:接地 触指发热 过电压 绝缘击穿 

分 类 号:TM763[电气工程—电力系统及自动化]

 

参考文献:

正在载入数据...

 

二级参考文献:

正在载入数据...

 

耦合文献:

正在载入数据...

 

引证文献:

正在载入数据...

 

二级引证文献:

正在载入数据...

 

同被引文献:

正在载入数据...

 

相关期刊文献:

正在载入数据...

相关的主题
相关的作者对象
相关的机构对象