作 者:隋翔龙 陆帅 谢伟 卞林林 周群 梁志 SUI Xianglong;LU Shuai;XIE Wei;BIAN Linlin;ZHOU Qun;LIANG Zhi(Nanjing Paneng Power Technology Development Co.,Ltd.,Nanjing 210000,China;State Grid Nanping Electric Power Co.,Ltd.,Nanping 353000,China)
机构地区:[1]南京磐能电力科技股份有限公司,江苏南京210000 [2]国网南平供电公司,福建南平353000
出 处:《电工技术》2024年第23期92-96,共5页Electric Engineering
摘 要:针对配电网在接入分布式电源(Distributed Generation, DG)后所带来的可靠性、选择性问题,为保证配电网供电系统的安全稳定运行,设计了一种基于面向通用对象的变电站事件(Generic Object Oriented Substation Events, GOOSE)通信的智能分布式保护系统。该系统通过GOOSE信号对配电网进行上、下分级处理,实现故障就近切除隔离的防越级跳闸功能。此外,系统配置暂态首半波能量法来实现小电流接地选线功能,能有效解决不接地系统发生单相接地故障后选线困难的问题。经过仿真模拟及现场试验表明,该系统能可靠防止越级跳闸及准确地进行单相接地选线,有效提高配电网供电可靠性。In response to the reliability and selectivity issues brought by the integration of Distributed Generation(DG)into the distribution network,and to ensure the safe and stable operation of the distribution network power supply system,this paper designs an intelligent distributed protection system based on General Object Oriented Substation Events(GOOSE)communication.The system uses GOOSE signals to perform hierarchical processing on the distribution network,achieving nearby disconnection,fault isolation,and preventing overstep tripping.In addition,the system adopts the transient first half wave energy method to achieve the small current grounding line selection function,which can effectively solve the problem of difficult line selection after single-phase grounding faults occur in ungrounded systems.The experiment shows that the system can effectively prevent the occurrence of overstep tripping accidents,and reliably select grounding lines when single-phase grounding,improving power supply reliability.
关 键 词:分布式电源 GOOSE通信 防越级保护 智能分布式保护 小电流接地选线
分 类 号:TM774[电气工程—电力系统及自动化]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.3