民用机场消防给水系统设计常见问题探讨  

Discussion on Common Problems of Civil Airport Fire Water Supply System Design

在线阅读下载全文

作  者:潘国庆 PAN Guo-qing(Zhongshe Antai(Beijing)Engineering Consulting Co.Ltd.,Beijing 100044,China)

机构地区:[1]中设安泰(北京)工程咨询有限公司,北京100044

出  处:《工程建设与设计》2025年第3期32-34,共3页Construction & Design for Engineering

摘  要:通过介绍机场飞行区消防给水系统设计,分析了塔台消防系统设置相关问题并提出解决方案。建议通用机场设置机坪及跑道消防给水系统,跑道消防应优先采用管道供水方式,消火栓间距应符合现行规范要求,跑道设计用水量应按所有消防车总数50%以上的车辆同时取水设计。This paper introduces the design of the fire water supply system in the airfield area of the airport,analyzes the problems related to the settingoftower fire control system and puts forward the solutions.Suggests that the general airport should set up the fire water supplysystem for the apron and the runway.The runway fire protection should give priority to the pipeline water supply,the distance between fire hydrants should meet the requirements of the current regulations,and the design water consumption of the runway should be designed according to the water intake ofmore than 50%ofthe total number offire trucks.

关 键 词:民用机场 消防给水 飞行区消防 跑道消防 塔台消防 

分 类 号:TU892[建筑科学]

 