检索规则说明:AND代表“并且”;OR代表“或者”;NOT代表“不包含”;(注意必须大写,运算符两边需空一格)
检 索 范 例 :范例一: (K=图书馆学 OR K=情报学) AND A=范并思 范例二:J=计算机应用与软件 AND (U=C++ OR U=Basic) NOT M=Visual
作 者:王磊 Wang Lei(Datong Hudong Power Generation Company of State Power Grid,Datong Shanxi 037043,China)
机构地区:[1]国电电力大同湖东发电有限公司,山西大同037043
出 处:《现代工业经济和信息化》2025年第2期270-271,276,共3页Modern Industrial Economy and Informationization
摘 要:针对火电厂低压厂用电系统发生单相接地越级跳闸故障,采用剩余电流型单相短路保护方案来过滤不平衡电流,提高灵敏度。选择零序电流保护方案,避免发生拒动情况。通过使用防越级跳闸保护系统,保证了火电厂供电系统正常运行时间延长至17530 h,故障发生率≤1.35%,大范围降低了运营成本。For the occurrence of single-phase ground tripping fault in the low-voltage power system of thermal power plant,residual current type single-phase short-circuit protection scheme is adopted to filter the unbalanced current and improve the sensitivity.The zero sequence current protection scheme is selected to avoid the occurrence of refusal.By using the anti-step trip protection system,it ensures that the normal operation time of the power supply system of the thermal power plant is extended to 17,530 h,and the fault incidence rate is≤1.35%,which reduces the operation cost in a wide range.
分 类 号:TM621[电气工程—电力系统及自动化]