作 者:郑大科 黎桂 唐晓磊 高吉祥 Zheng Dake;Li Gui;Tang Xiaolei;Gao Jixiang(Guangdong Shunguang Rail Transit Co.,Ltd.,Foshan;Foshan Rail Transit Design and Research Institute Co.,Ltd.,Foshan)
机构地区:[1]广东顺广轨道交通有限公司,佛山 [2]佛山轨道交通设计研究院有限公司,佛山
出 处:《暖通空调》2025年第3期147-152,69,共7页Heating Ventilating & Air Conditioning
摘 要:以夏热冬暖地区投入运行的某地铁车站为例,对直膨式蒸发冷凝空调系统进行了实测研究,分析了影响系统COP的主要因素,对系统进行了实测优化研究,包括末端风机采用变频运行策略和对蒸发冷凝器进行除垢,并与同一线路采用冷却塔与冷水机组作为冷源的常规车站进行了对比分析。结果表明:直膨式蒸发冷凝空调系统的制冷系统COP为4.55,低于同一线路常规冷源车站的5.24;末端风机采用变频运行策略后节能效果显著,车站公共区温度、CO_(2)体积分数基本维持在设计工况,制冷系统压缩机能耗降低了9.6%,末端风机能耗降低了21.0%,车站单端制冷系统COP由2.88升高到3.47,提升了20.5%;对蒸发冷凝器除垢后,车站单端制冷系统COP由3.49提高到4.24,提升了21.4%。Taking a subway station operating in the hot summer and warm winter zone as an example,this paper conducts experimental research on the direct expansion evaporative condensation air conditioning system,and the main factors affecting the COP of the system are analysed.The optimized study is carried out on the system,including adopting the frequency conversion operation strategy for the terminal fans and descaling the evaporative condensers.The comparison is made with a conventional station using cooling towers and chillers as cold sources on the same line.The results show that the refrigeration system COP of the direct expansion evaporative condensation air conditioning system is 4.55,which is lower than 5.24 of the conventional cold source station on the same line.After adopting the frequency conversion operation strategy for the terminal fans,the energy-saving effect is significant,the temperature and the CO_(2) volume fraction in the public area of the station are basically maintained at the design conditions,the energy consumption of the refrigeration system compressor is reduced by 9.6%,the energy consumption of the terminal fans is reduced by 21.0%,and the COP of the single-end refrigeration system of the station is increased from 2.88 to 3.47 with an increase of 20.5%.After descaling the evaporative condensers,the COP of the single-end refrigeration system of the station is increased from 3.49 to 4.24 with an increase of 21.4%.
关 键 词:地铁车站 直膨式空调 蒸发冷凝 实测 优化 性能系数(COP) 变频运行 除垢
分 类 号:TU962[建筑科学] U231.4[交通运输工程—道路与铁道工程]
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在载入数据...
正在链接到云南高校图书馆文献保障联盟下载...
云南高校图书馆联盟文献共享服务平台 版权所有©
您的IP:216.73.216.7